KOREAN
ENGLISH
ENG

4-conductor spacer damper set

SB-11

SB-11

SB-14

SB-14

Damper
Function and use
Device used to prevent towers from collapsing due to sub-span vibrations of power lines. Sub-span vibrations are said to occur at wind speeds above 10 m/s, but in practice, vibration amplitude is significantly dampened by the installation of spacer dampers
Product Category Product
Stockbridge damper SB-AC240
SB-AC410
SB-AC480
4-Conductor spacer damper 4-conductor spacer damper for 345kV high-capacity conductor

Types and Specifications

KEPCO Engineering Standard Item Number Model Damper Specification Applicable
Line (mm²)
Remarks
(ACSR equivalent standard)
Counterweight Mass Armour Rod Length
GS-5340-0055
: Stockbridge Damper for Aluminium Stranded Conductors
127070 SB-AC240 5.5kg 500mm ASCC 290 (Carbon-metal)
ASCC 310 (Carbon-glass)
ACMR 240
240mm²
ASCC 330 330mm²
127071 SB-AC410 6.4kg 600mm ASCC 410 (Carbon-metal) 330mm²
ASCC 430 (Carbon-glass)
ACMR 410 410mm²
ACMR 440 480mm²(R)
127072 SB-AC480 7.3kg 660mm ASCC 500 (Carbon-metal) 410mm²
ASCC 520 (Carbon-glass)
ASCC 520 (Carbon-metal) 480mm²
ASCC 540 (Carbon-glass)
KEPCO Engineering Standard Item Number Model Applicable Line Rotational Angle Sub-conductor Spacing
(Between Conductor Centers)
Conductor Clamping Force ACSR Equivalent Standard (mm²)
Type (mm²) Outer Diameter (mm)
GS-5975-0214
: Capacity-Enhanced 4-Conductor Spacer Damper for Aluminium Stranded Conductors
127302 TSAS-430 ASCC 430 25.14 At least ±30° 400±3mm 200kgf 330
128309 TSAS-410L ASCC 410L 25.14
127303 TSAC-330 ACMR 330 23.2
127304 TSAS-520 ASCC 520 28.14 At least ±30° 400±3mm 200kgf 410
128310 TSAS-500L ASCC 500L 28.14
127305 TSAC-410 ACMR 410 26.0
127306 TSAS-540 ASCC 540 28.63 At least ±30° 457±3mm 200kgf 480
128311 TSAS-520L ASCC 520L 28.71
127307 TSAC-440 ACMR 440 26.2